RESIDENTIAL ESS
RoveGEL · DG12-60
12 V / 60 Ah
DG12-60
- Chemistry
- Deep-cycle GEL VRLA
- Nominal voltage
- 12 V
- Rated capacity
- 60 Ah

Technical specifications.
Specifications · page 1
| Cells Per Unit | 6 |
|---|---|
| Voltage Per Unit | 12 |
| Capacity | 60Ah@20hr-rate to 1.75V per cell @25°C |
| Weight | Approx. 20.5 kg (Tolerance ±3.0%) |
| Internal Resistance | Approx. 8.5 mΩ |
| Terminal | F15(M6) / F11(M6) |
| Max. Discharge Current | 600A (5 sec) |
| Design Life | 15 years (floating charge) |
| Maximum Charging Current | 12.0 A |
| Reference Capacity | C3 40.8Ah |
| C5 47.2Ah | |
| C10 52.6Ah | |
| C20 60.0Ah | |
| Float Charging Voltage | 13.6V~13.8V @25°C Temperature Compensation: -3mV/°C/Cell |
| Cycle Use Voltage | 14.2V~14.4V @25°C Temperature Compensation: -4mV/°C/Cell |
| Operating Temperature Range | Discharge: -40°C~60°C |
| Charge: -20°C~50°C | |
| Storage: -40°C~60°C | |
| Normal Operating Temperature Range | 25°C ± 5°C |
| ROVON Valve Regulated Lead Acid (VRLA) batteries can be stored | |
| for up to 6 months at 25°C and then recharging is recommended. | |
| Self Discharge | Monthly Self-discharge ratio is less than 3% at 25°C. Please charge |
| batteries before using. | |
| Container Material | A.B.S. UL94-HB, UL94-V0 Optional |